Coil Specifications
printer friendly version (pdf)
Fin Materials
.006, .008, and .010”
Aluminum and Copper
Fin Spacing
1/2" OD Tubing - 12 to 16 fins per inch
5/8” OD Tubing - 6 to 14 fins per inch
3/8" OD Tubing - 10 to 20 fins per inch
Tube Material
3/8” OD x .016” Wall -Copper
1/2” OD x .016”, .020” Wall - Copper
5/8” OD x .020”, .025”, .035”, .049” - Copper
Casings
16 and 14 Gauge Galvanized Steel
16 Gauge 304 and 316 Stainless Steel
.06 or .09 inch copper
Headers
Type “L” or “M” from 7/8” OD to 4 1/8” OD Copper
Connections
Water and Steam Coils – Copper, Steel, or Brass
MPT or FPT Connections
DX Distributors – Standard or Hot Gas
DX, Condenser and Heat Reclaim – Copper Sweat Connections
Supply Connections on both ends of Steam Distributing Coils
Testing
All coils are leak tested under water at 450 PSIG dry nitrogen
Other Options
Non-Standard Casing Flange Widths and Casing Depths
Special Coil Coatings
Additional Distributors
Non Standard Circuiting
Intertwined Circuiting (DX Only)
Insulated Coil Sections
Premium Ship Time Program
Precision Coils Tube Patterns


|